Print the card
CAAI
Description
Instantaneous industrial relay with magnetic arc blowing for high contacts rating.
Pluggable on sockets with a withdrawal clasp and square guide pins which will act as a key to ensure that the correct relay is used at the correct voltage (see our withdrawal guide in the technical support pages of this site)
Pluggable on the following sockets : EVB1/CA, ERDL1/CA, ERDL1/CA-DL et ERC1/CA.
Dimensions
Connection
Technical features
Function |
Instantaneous |
Presentation |
under cover |
Connection |
on front or rear wiring socket |
Number of mechanical operations |
30.000.000 |
Operating temperature |
- 5 to + 40°C |
Storage temperature |
- 40 to + 70°C |
Climatic protection |
optional reinforced climatic protection |
Shock voltage |
5 KV (wave 1,2/50 µs) |
Dielectric strength |
2500 V eff 50 Hz |
Insulation resistance |
NFC 45-202 : C500 ; VDE0100 : C380 |
Weight |
200 g. |
Protection level |
IP 40 (according to NFC 20-010) |
Resistance to mechanical shocks |
severity 50 A (according to NFC 20-608) |
Resistance to vibrations |
0,35 mm / 10-55 Hz (according to NFC 20-616) |
Coil data
|
Direct current |
Alternative current |
Min. nominal voltage DC |
6 V |
6 V |
Min. nominal voltage AC |
220 V |
380 V 50/60 Hz |
Operating range |
-20/+10% of nominal voltage |
Power requirement |
3 W +/- 10% |
|
|
Contacts
Number of contacts |
4 |
Max. load current |
8 A per contact |
Low power switching |
0,1 VA with min. voltage 1 V and/or I min 1 mA |
Response time (bounce time not included) |
AC/DC < 28 ms |
Contacts rating
DIRECT CURRENT |
resistive load - connection on DC - Comparison CAA-CAAI |
Connection on DC - CAAI alone |
|
|
|
Versions
. CAAI relay with reinforced climatic protection
. CAAI relay with specific characteristics (voltage, frequency)
. CAAI intensity relay
. CAAI dual voltage relay
. CAAI relay with internal protection by varistor or diode
. CAAIJ relay with mechanical indicator
Homologations & conformities :
* CEI 255-1-00
* NFC 45-250 & 20-618 (solderability)
Non-contractual document - characteristics to be confirmed before order
TEC AUTOMATISMES reserves the right to modify description and specifications without notice