Print the card
GAP
Description
Impulse relay - 4 CO contacts - 3 A.
Pluggable on socket with possible withdrawal clasp. Pins at the standard pitch of 2.54 mm. Possibility of polarizatio by mounting a male withdrawal clasp on the relay and a female withdrawal clasp on the socket.
GAP relay is pluggable on the following sockets : EVB/GE, 9877, EVC/GE, 9876, ER/GE 2.8, or ER/GE.
Dimensions
Connection
Operation principle
Functions :
* ET : impulse on voltage application
* MT : impulse on voltage lack
Duration of impulse contact : 0,15 to 1 s
Interval between 2 operations : > 1 s
Technical features
Function |
impulse (ET - MT) |
Presentation |
under cover |
Connection |
on front or rear wiring socket |
Number of mechanical operations |
30.000.000 |
Operating temperature |
- 5°C to + 40°C |
Storage temperature |
- 40°C to + 70°C |
Climatic protection |
optional reinforced climatic protection |
Dielectric strength |
2000 V eff-50 Hz |
Insulation resistance |
NFC 45-202 : C 250 V |
Weight |
60 g. |
Protection level |
IP40 (according to NFC 20-010) |
Resistance to mechanical shocks |
severity 50 A (NFC 20-608) |
Resistance to vibrations |
frequency range : 10-55 Hz (NFC20-616) |
Coil data
|
Direct current |
Alternative current |
Min. nominal voltage DC |
24 V |
24 V |
Min. nominal voltage AC |
230 V |
230 V |
Operating range |
-20/+10% of nominal voltage |
Power requirement |
ET : 2 W - MT : 0,5 W |
|
|
Contacts
Number of contacts |
4 |
Max. load current |
3 A |
Low power switching |
0,1 VA with min voltage 1 V and/or I min 1 mA |
Response time (bounce time not included) |
< 14 ms |
Contacts rating
DIRECT CURRENT |
connection on DC |
|
|
ALTERNATIVE CURRENT |
connection on AC |
|
|
Versions
. GAP relay with reinforced climatic protection
. GAP relay with specific voltages.
Homologations & conformities :
NFC 45-250
CEI 255.1.00
Non-contractual document - characteristics to be confirmed before order
TEC AUTOMATISMES reserves the right to modify description and specifications without notice