Imprimir
Application
Object : Releases and pilots the whole start sequences of a high and medium power generating set. The sequences can be caused by : the local power supply stop, top EJP operation, test, ... This PLC can be plugged on a network (modbus dialogue), questioned by a supervisor via the comuted network.
Particularities :
. Admits important voltage drops at the generator\'s start,
. Measures the frequency of the voltage delivered by the generating set,
. IP 65 sealed front face,
. defaults statement,
. Programming through ALOGRAF software,
. Supervision with CITECT software.
Conception
Power supply :
* 12 or 24 VDC
Inputs :
* 16 digital inputs 12/24 VDC
* 2 analog inputs 150/415 VAC
* 1 digital frequency input 8/80 Hz.
Outputs :
* 8 static outputs 60 mA for remote relays control
* 8 static outputs 0,5 mA open collector
* 1 static output 125 mA for alternator\'s excitation
* 1 RS232C output for loading and supervision
Dimension :
* 290 x 170 x 125 mm
Composants
* Microprocessor INTEL 16 bits 80C196
* "FLASH" PLC memory
* HCMOS logic
* Retro-lighted display of 2 lines of 16 characters
Document non-contractuel - Caractéristiques à se faire confirmer avant commande
Tec automatismes se réserve le droit de modifier les descriptions et spécifications sans préavis