TEC AUTOMATISMES

Bienvenido Productos Relais instantanés et de Fonction Instantaneous relays 4 contacts BA

Relais instantanés et de Fonction

Imprimir

Description

Instantaneous relay with high contact rating.

Relay pluggable on socket including a withdrawal clasp and two square guide pins which can ast as a key to ensure that the correct relay is used at the correct voltage.(see our withdrawal guide in the technical support pages of this site)

Recommended operating position : vertical coil axle/clapper upside or horizontal coil axle/contacts down.

Pluggable on front wiring socket (EVD) or rear wiring sockets (ER, ERB, ERDL).

Encombrement

Raccordement

Principe de fonctionnement

This relay is equipped with 5 double cut-off CO contacts with self arc blowing, particularly adapted to high DC cut-off.

Minimum switching current :

* up to 12 V : not recommended
* 160 mA at 24 V
* 55 mA at 48 V
* 8 mA at 125 V
* 0,9 mA at 220 V
* 0,1 mA at 380 V

Caractéristiques

Fonction Instantaneous
Présentation under cover
Raccordement on front or rear wiring socket
Nombre de manoeuvres mécaniques 50.000.000
Température de fonctionnement - 5??C to + 40??C
Température de stockage - 40??C to + 70??C
Catégorie climatique optional reinforced climatic protection
Tension de choc 5 KV (wave 1,2/50 ??s)
Rigidité diélectrique 2500 V eff
Résistance d'isolement C500 (according to NFC 45-202 & VDE 0110)
Masa 300 g.
Degré de protection IP 40 (according to NFC 20-010)

Bobine

  Courant continu Courant alternatif
Tension nominale mini. 6 V 6 V
Tension nominale maxi. 220 V 380 V - 50/60 Hz.
Domaine d'action -20/+10% of nominal voltage
Classe de puissance 3 W +/- 10% 14 VA +/- 20% 7,5 VA +/- 20%

Contactos

Número de contactos 4
Courant permanent maxi. admissible 10 A per contact
Temps de réponse (rebonds non-inclus) DC < 36 ms - AC < 31 ms

Pouvoir de coupure

COURANT CONTINU
connection on DC

Versions

BA72: DC versions
BA88: AC versions
 
 
Other versions:
 
. Relay BA with reinforced climatic protection
. Relay BA with specific characteristics upon request
. Relay BA UIC (for SNCF use)
. BA intensity relay (for DC)

Homologations & conformities :

* CEI 255-1-00
* NFC 45-250

Document non-contractuel - Caractéristiques à se faire confirmer avant commande
Tec automatismes se réserve le droit de modifier les descriptions et spécifications sans préavis

TEC Automatismes © 2024, Tous droits réservés