Print the card
CACTA-Z04AA
Description
Electronic timer relay adjustable from 0.2 to 300 Sec in three ranges - 2 timed contacts / 2 instantaneous contacts - 3 A.
To substitute the obsolete BC relay
Pluggable on socket with a withdrawal clasp and square guide pins which can act as a key to ensure that the correct relay is used at the correct voltage (see our withdrawal guide in the technical support pages of this site)
Pluggable on the following sockets : EVB1/CA, ERC1/CA, ERDL1/CA.
Dimensions
Connection
Operation principle
Functions :
* ET : timed on voltage application
* MT : timed on voltage lack
Timing (3 ranges) adjustable by potentiometer on front face :
* 0,2 to 3 s
* 2 to 30 s
* 20 to 300 s
operation accuracy : +/- 5%
Fidelity : 2% at 20°C
Recycling time >= 50 ms
minimum supply time (MT function) : 500 ms
Technical features
Function |
timer (ET, MT) |
Presentation |
under cover |
Connection |
on front or rear wiring socket |
Number of mechanical operations |
30.000.000 |
Operating temperature |
- 5°C to + 40°C |
Storage temperature |
- 40°C to + 70°C |
Shock voltage |
3 KV (wave 1,2/50 µs) |
Dielectric strength |
1000 to 2200 V eff |
Weight |
300 g. |
Protection level |
IP 40 (according to NFC 20-010) |
Resistance to mechanical shocks |
severity 50 A (NFC 20-608 & CEI 68-2-6) |
Resistance to vibrations |
0,35 mm / 10-55 Hz |
Coil data
|
Direct current |
Alternative current |
Min. nominal voltage DC |
24 V |
24 V |
Min. nominal voltage AC |
230 V |
230 V |
Operating range |
-20/+10% of nominal voltage |
Power requirement |
3 W |
|
|
Contacts
Number of contacts |
2 |
Max. load current |
3 A per contact |
Low power switching |
0,1 VA with min. voltage 1 V and/or I min 1 mA |
Contacts rating
DIRECT CURRENT |
connection on DC |
|
|
ALTERNATIVE CURRENT |
connection on AC |
|
|
Versions
Homologations & conformities :
* CEI 255-1-00
* NFC 45-250
Non-contractual document - characteristics to be confirmed before order
TEC AUTOMATISMES reserves the right to modify description and specifications without notice