Print the card
CAQ
Description
Instantaneous relay with rapid memory.
Pluggable on socket with a withdrawal clasp and square guide pins which can act as a key to ensure that the correct relay is used at the correct voltage (see our withdrawal guide in the technical support pages of this site)
Pluggable on the following sockets : EVB2/CA, ERC2/CA or ERDL2/CA.
Dimensions
Operation principle
This relay is a rapid memory which acts when it receives an impulse with duration > 0.5 ms (terminal 14). This information is re-sent (tipping of the two CO contacts) when validated by action on terminal 13 (validation). This information is directly re-sent il terminals 13 and 15 are linked. Return to rest state is made by cutting-off terminal 15 (reset).
See the operation diagram hereafter
Technical features
Function |
instantaneous |
Presentation |
under cover |
Connection |
on front or rear wiring socket |
Number of mechanical operations |
35.000.000 |
Operating temperature |
- 5°C to + 40°C |
Storage temperature |
- 40°C to + 70°C |
Climatic protection |
optional reinforced climatic protection |
Shock voltage |
3 KV (wave 1,2/50 µs) |
Dielectric strength |
2200 V eff |
Weight |
200 g. |
Protection level |
IP 40 (according to NFC 20-010) |
Resistance to mechanical shocks |
severity 50 A (according to NFC 20-608) |
Resistance to vibrations |
0,35 mm / 10-55 Hz (according to NFC 20-616) |
Coil data
|
Direct current |
Alternative current |
Min. nominal voltage DC |
12 V |
|
Min. nominal voltage AC |
220 V |
|
Operating range |
-20/+10% of nominal voltage |
Power requirement |
4 W permanently - 0,5 W control impulse |
|
|
Contacts
Number of contacts |
2 |
Max. load current |
8 A per contact |
Low power switching |
0,1 VA with min voltage 1 V and/or I min 1 mA |
Contacts rating
DIRECT CURRENT |
Power supply in DC - connection on DC |
Power supply in AC - connection on DC |
|
|
|
ALTERNATIVE CURRENT |
power supply in AC or DC - connection on AC |
|
|
Operation diagram
see detailed operation diagram here above
Versions
. CAQ relay with reinforced climatic protection
. CAQP relay with control by positive polarity
. CAQN relay with control by negative polarity
. CAQ relay with impulse < 0,5 ms
Non-contractual document - characteristics to be confirmed before order
TEC AUTOMATISMES reserves the right to modify description and specifications without notice