Print the card
1275
Description
Instantaneous relay 1, 2 or 3 CO contacts.
Pluggable on front wiring socket (9976) or rear wiring socket (9274)
Detailed table of coil resistance data is available in the technical support pages of this site or can be sent upon request.
Dimensions
Connection
Technical features
Function |
instantaneous |
Presentation |
under cover |
Connection |
on front or rear wiring socket |
Number of mechanical operations |
10.000.000 |
Operating temperature |
- 10 to + 40°C |
Storage temperature |
- 40°C to + 80°C |
Climatic protection |
reinforced climatic protection |
Shock voltage |
15 g - 11 ms |
Dielectric strength |
2 KV-50 Hz-1 min at 40°C and 70% HR |
Insulation resistance |
200 MOhms |
Weight |
67 g. |
Coil data
|
Direct current |
Alternative current |
Min. nominal voltage DC |
6 V |
6 V |
Min. nominal voltage AC |
220 V |
400 V |
Operating range |
-15/+10% of nominal voltage |
Power requirement |
3 inv : 1,2 to 2,2W |
3 to 4,5 VA |
1,6 to 3 VA |
Contacts
Number of contacts |
1, 2 or 3 |
Max. load current |
10 A per contact |
Low power switching |
40 mA min for 6 V |
Short-circuit load |
250 A / 30 ms |
Response time (bounce time not included) |
DC < 20 ms - AC < 25 ms |
Bounce time |
< 7 ms |
Contacts rating
DIRECT CURRENT |
resistive load |
inductive load L/R = 20 ms |
|
|
|
ALTERNATIVE CURRENT |
resistive load |
inductive load cos phi = 0.7 |
|
|
|
Versions
In spite of its very reduced dimension, this relay offers the maximum number of characteristics.
This relay can also be directly mounted with single tab terminal for 4.75 x 0.5 clips (please contact us).
Non-contractual document - characteristics to be confirmed before order
TEC AUTOMATISMES reserves the right to modify description and specifications without notice